RS AGP AQP Series

ARDO CBR (Copper Bonded Rod)

Product Datasheet

 


 

RS AGP / RS AQP -X1-X2 X3-X4

RS AGP and RS AQP Series protector

G (Q) : G- Gas discharge type Q 1/4 wavelength type

Maintenance Free
X1: connection type’ major have BNC TNC SMA NF 7/16 etc.
X2:  Transmission Impedance, 50 Ohm and 75 Ohm
X3: connection type - M(male)and F (female)
X4:  special indication, for example, 1/4 wavelength 900/1800 - it indicate the operating frequency
 

Gas Discharge Type Coaxial protection technology

The gas discharge tube under the normal condition is one kind of insulator, which is parallel to the protected equipment. When the overvoltage is happened, when the gas discharge tube has achieved the impulsive discharge voltage, it will have the short circuit in a short time, it will drain the surge into the grounding system safety, after that, the gas discharge tube will restore to the state of insulation.

Gas Discharge type can be replaced, for maintenance
Common characteristic :
 ◆ VSWR < 1.2
 ◆ Insertion Loss < 0.2dB
 ◆ Bandwidth 0 to 3GHz
 ◆ Max. Discharge current Imax:20kA (8/20)
 ◆ connector:7/16, N, BNC, TNC, SMA, UHF, 7/8                  cable,

 

 

 

                                               

 

 

 

 

Model

RS AGP-BNC-75MF

RS AGP-BNC-50MF

RS AGP-TNC-50MF

RS AGP-N-50MF

RS AGP-SMA-50MF

RS AGP-F-50MF

RS AGP-7/16-50MF

Connector type

BNC-MF

BNC-MF

TNC-MF

N-MF

SMA-MF

F-MF

7/16-MF

FrequencyGHz

0 – 2.5

0 – 2.5

0 – 2.5

0 – 2.5

0 – 2.0

0 – 2.0

0 – 2.5

impedance( Ohm )

75

50

50

50

50

75

50

Operating voltage

90V&230V

90V&230V 、350V

Max. Discharge Current

20KA(8/20μs)

Residual voltage

≤600V (1KV/μs)

VSWRVSWR

≤1.2

Insertion Loss

≤0.2dB

Temperature

-40℃ ~+85℃

Insulation Resistance

10

 

 

RS AGP-G-BNC-50MF

 

 

 

 

RS AGP-G-7/16-50MF

             

 

 

 

RS AGP-G-N-50MF

 

 

 

 

 

RS AGP-G-F-75MF

 

 

 

 

 

 

 

1/4 Wavelength Coaxial Protection technology


       Another solution is not the gas Discharge tube, and it is Coaxial Quarter Wave Lightning and surge Protection.
  This protector have the short circuit mechanical system to connect tot the outside ground system, it have filter function and adjust the mechanical dimension can provide the narrow or width band function., So this protector can be narrow band or wide band. Because the lightning bandwidth is low, this protector can eliminate the noise out of the normal signal.
Specification
◆ VSWR < 1.2
◆ Insertion Loss < 0.2dB
◆ Bandwidth is narrow band,such as Mobile Telecom application, 900MHz and1800MHz
◆ Max. Discharge Current Imax:100kA (8/20uS)
◆ Connector:7/16, N, TNC 

 

 

 

 

Model

RS AQP-N-50MF-900/1800

RS AQP-7/16-50MF-900/1800

RS AQP-TNC-50MF-900/1800

RS AQP-7/16-50MF-450

RS AQP-N-50MF-2400

RS AQP-N-50MF-5800

Connection type

N-MF

7/16-MF

TNC-MF

7/16-MF

N-MF

N-MF

Frequency GHz

0.8-1.0/1.7-1.9

0.8-1.0/1.7-1.9

0.8-1.0/1.7-1.9

0.8-1.0/1.7-1.9

0.8-1.0/1.7-1.9

0.8-1.0/1.7-1.9

Impedance Ohm

50

50

50

50

50

50

Max. Discharge

Current

100kA,8/20μs

50kA,8/20μs

50kA,8/20μs

50kA,8/20μs

50kA,8/20μs

50kA,8/20μs

Residual voltage

≤10V (1KV/μs)

VSWR

≤1.15

Insertion Loss

≤0.2dB

Temperature

-40℃ ~+85℃

Insulation Impedance GΩ

10